CITY GAS DISTRIBUTION (Energy that creates a better path)

Sunday, May 9, 2021

Commercial NG Burners

 High Pressure Burners (T Type)

Burner Type

Consumption (Kgs/Hr)

T-22

0.9

T-35

1.58

T-50

2.24

T-78

3.56


Avg Load that has to be considered for HP burners is 2 SCMH  


High Pressure Burners (M Type)


Burner Type

Consumption (Kgs/Hr)

M-22

0.9

M-35

1.58

M-50

2.24

M-78

3.56




 V Burner

            

Burner Type

Consumption (Kgs/Hr)

V-300

1.58

V-600

1.58

V-900

1.58

V-1200

1.58




Bunsen Burner (Laboratory Burner)


Consumption - 0.3(Kgs/Hr)

Meters & regulators for I&C Connections & Type of Consumers

Commonly used meters & regulators for I&C Connections 

Tentative
Load SCMH

Meter Size
SCMH

Regulator Size SCMH

Regulator Type

Operating
Pressure mBar

Upto 2.5

3.

3.

Domestic

21

2.5 - 6

6

10

Module / Riser

100

6 - 10

10

10

Module / Riser

100

10 - 25

25

25

Module / Riser

100

25 - 40

40

40

Riser

100

40 — 65

65

65

Riser

100

Above 65

Combination
of above

Combination
of above

Module / Riser

100

Above 65

Customized

Customized

MRS

100 - 500

 









Sunday, April 4, 2021

CRITERIA FOR SELECTION OF METER

  •  Contractual requirement
  •  Rangeability or Turndown ratio
  •  Accuracy required
  •  Pressure requirement
  •  Calibration & maintenance requirement
  •  Size & weight
  •  Installation and maintenance constraints
  •  Operability
  •  Cost
  •  Gas quality
RANGEABILITY

The ratio between Qmin and Qmax, i.e. the minimum and maximum flow rate

respectively for which the meter performs within the maximum permissible errors.

For various type of meters are as follows,

  • Diaphragm meters 1: 150
  • Rotary Positive Displacement meters 1:30 or Better
  • Turbine 1:30 or Better

FILTRATION

Filtration at 50 microns or finer should be fitted to all metering system operating

at pressure above 500 mbar and 27 deg C.

CORRECTORS

Electronic volume correctors will be fitted to all meters operating between flow

range of 800 to 2500 scmd and for flow range above 2500 scmd Electronic flow

meter will be used.

GUIDANCE ON SELECTION

1. Commercial A (Up to 200 scm per day)

a. Normal Commercial :- Small Cafeterias, Restaurants, Caterers, SSI’s etc.

b. Small Commercial :- Office kitchen / Pantries.

c. Concessionary Commercial:- Temples, Charitable trust, Govt. Institution, etc


2. Commercial B (5000 to 25000 SCM per month)

Small scale commercial establishment and industries.


3. Commercial C (above 1000 scm per day)

Big hotels, commercial establishment , hospitals etc.


4. Commercial AC (Only for > 200 TR VAM)

Big hotels, commercial establishment , hospitals etc


5. Industries (Above 1000 SCM per day)

Search Blog

CITY GAS DISTRIBUTION

Flange

A flange is a method of connection pipes, valves, pumps, and other equipment to form a piping system. It is the second and most connection a...

POSTS